LIU Jiang, YAN Si-an, LI Chuan, et al. Effect of climate conditions monitored by FBG sensors on electricity tower cross arm strain[J]. 2014, 33(4): 62-64.
LIU Jiang, YAN Si-an, LI Chuan, et al. Effect of climate conditions monitored by FBG sensors on electricity tower cross arm strain[J]. 2014, 33(4): 62-64. DOI: 10.13873/j.1000-97872014.04.010.
During process of electric power tower cross arm long-term operation
the stress of insulation cross arm change complex. Real-time monitoring on cross arm stress is an important factor that ensure long-term security and stability of tower cross arm. Put forward a kind of fiber Bragg grating( FBG) strain sensor which can transform stress variation beared by cross arm into wavelength shift of FBG
and applied in substation of power tower. According to the climatic feature of Yan Jin transformer substation
install four strain sensors in the center of the tower truss material up and down surface. Aiming at the climatic conditions on February
2011
stra
in monitoring range is- 58. 05 × 10- 6
-
242. 52 × 10- 6; snow
rain weather occur at 10 o’clock
on January 12
2011
the strain monitoring range is- 93. 71 × 10- 6
-
3. 46 × 10- 6and four strain sensors simultaneously fluctuations at the same time. The experiment indicates that in normal circumstances
cable dance
snow
rain and other weather conditions are the important factors which cause cross arm deformation of tower.