ZHANG Ying-chao, WANG Fei-fan, LIAO Jun-ling, et al. Research on heating control of double heating radiosonde humidity sensor[J]. 2013, 32(8): 47-49. DOI: 10.13873/j.1000-97872013.08.038.
A method for calculation of actual relative humidity of heated twin radiosonde capacitive humidity sensor without inference of heater is analyzed and constructed based on relationship between relative humidity
temperature
dew point and saturation vapor pressure before and after heating.Fuzzy RBF neural network PID control method is used to control the heater
avoiding of complicated manual PID parameters tuning process.Matlab simulation results indicate that
compared with traditional PID controller using Niegler-Nichols empirical formula
the fuzzy RBFPID controller has better stability and faster response speed
its step response overshoots are 15.1 %
4.3 % respectively
settling times under permissible error of 2 % are 7.12