ZHAO Li-hua1, LI Yang-liu2, LI Guo-qiang2. Study of on-line transformer DGA system based on gas sensor[J]. 2009, 28(11): 46-48. DOI: 10.13873/j.1000-97872009.11.001.
基于气体传感器的变压器在线DGA系统的研究
摘要
设计的在线溶解气体分析(DGA)系统采用高分子膜提取油中溶解气体
利用气体传感器对气体体积分数进行检测
使用无线通信模块将气体体积分数信息传输到主控室的计算机上。与离线色谱相比
在气体体积分数测量范围为(4
2
00)×10-6
对H2测量最大绝对误差为2×10-6
对CO测量在(100
2
000)×10-6的最大绝对误差为30×10-6
可以达到对变压器油中溶解气体进行在线监测分析的要求。
Abstract
To satisfy this requirement
most of the electrical utilities run standard dissolved gas analysis(DGA).As summarizing disadvantage of current theories used in real-time gas concentration measurement
an on-line DGA system which mounted PTFE membrane
gas sensors
weak signal detection module
wireless communication module is developed.Compared with GC result of DGA
for hydrogen detection
the biggest error of the system is 2×10-6 at rang of(4
2
00)×10-6;for carbon monoxide detection
the biggest error of the system is 30×10-6 at range of(100
2
000)×10-6.The system can meet the requirement of on-line DGA.An additional potential of cost reductions and safely improvements can be achieved.