CHEN Wu-fen, LIU Ai-lian, LI Ying-na, et al. Research on wireless ultrasonic sensor networks in switchgear partial discharge on-line monitoring[J]. 2015, 34(3): 31-33.
CHEN Wu-fen, LIU Ai-lian, LI Ying-na, et al. Research on wireless ultrasonic sensor networks in switchgear partial discharge on-line monitoring[J]. 2015, 34(3): 31-33. DOI: 10.13873/j.1000-9787(2015)03-0031-03.
Switchgear partial discharge is an important factor which causes switchgear insulation aging that leads to power accident. Combined with lumbar station substation project
3 ultrasonic sensors are mounted on the joint of 35kV switchgear and cable channel
and switchgear partial discharge is on-line detected. The partial discharge phenomenon occurs with the process of sound physical transformation
according to quantitative and qualitative relations of ultrasonic wave characteristics and partial discharge
insulation condition of switchgear will be detected and diagnosed. Monitoring data show that ultrasonic wave sensor numerical range is 204
422mV. In a certain extent
data curves reflects change of switchgear partial discharge
and provi
des effective support for further power fault forecasting.