GONG Bing, WANG Ke-jun, MA Xiao-wei. Application of DSOGI-PLL algorithm in unbalanced and distorted grid voltage monitoring[J]. 2015, 34(1): 154-156+160.
GONG Bing, WANG Ke-jun, MA Xiao-wei. Application of DSOGI-PLL algorithm in unbalanced and distorted grid voltage monitoring[J]. 2015, 34(1): 154-156+160. DOI: 10.13873/J.1000-9787(2015)01-0154-03.
In order to ensure normal operation of grid-connected power converters under unbalanced
harmonic or distorted grid-voltage conditions
phase-locked loops( PLL)
which are able to accurately and rapidly detect phase and frequency of positive-sequence components for power signals at the fundamental frequency are in great need.Conventional synchronous reference coordinate-PLL( SRF-PLL) fails to satisfy the requirements due to its poor performance in harmonic suppression. Present a novel dual second-order generalized integrator-PLL( DSOGI-PLL)algorithm. By introducing frequency-locked loop( FLL)
DSOGI-PLL is frequency adaptive. Simulation and experimental results demonstrate that the algorithm can avoid effect of negative components of grid voltages and succeed in harmonics suppressing.